Acceleration Adjustments Ramp types
Voltage ramp or current ramp Starting torque 0 - 100% of line voltage or 0 - 600% of FLA Ramp time 1 to 120 seconds Current limit 200 - 600% |
Retentive Thermal Memory
Overload circuit retains thermal condition of the motor regardless of control power status. Unit uses real time clock to adjust for off time |
Deceleration Adjustments
Begin decel level 0 - 100% of line voltage
Stop level 0 to 1% less than begin decel
Decel time 1 - 60 seconds |
Phase Current Imbalance/Loss Protection
Imbalance trip level 5 - 30% current between any two phases Imbalance trip delay 1 - 20 seconds
Electronic Shear Pin Protection Shear pin trip level 100 - 300% of motor FLA Shear pin trip delay 1 - 20 seconds |
Kick Start Settings
Kick Voltaqe 10 - 100%
Kick start time 0.1 - 2 seconds |
Starts-per-Hour Lockout Timer
Starts-per-hour 1 - 10 successful starts per hour
Time between starts 1 - 60 min. between start attempts
|
Programmable Output Relays
Protection 4 relays; 1 Form C (DPDT), 3 Form A (SPST NO)
5A 240VAC max. (1200VA),
Individually programmable to 19 functions |
Event History
Up to 60 events; data includes event, time, date and current for each phase and ground fault current at time of event
Options
Ground Fault: Residual or Zero Sequence
RTD Inputs: Up to 12 RTD’s of any type with biasing or override protection curve |
Protection
Start & Run Protection
Two programmable overload trip curves allow for the thermal capacity required to start the load while providing motor overload protection needed during the run time.
Start: Programmable for Class 5 - 30
Run: Programmable for Class 5 - 30, enabled when starter detects motor is "At-Speed"
Reset: Manual or automatic, selectable via programming
The DXT Series recognizes motor cool-down rates are a function of the run time and that sometimes a motor will cool faster if allowed to run. |
Metering Functions
Motor Load: Percent of FLA
Current Data: A, B, C Phase Current, Avg Current, Ground Fault
Thermal Data: Remaining thermal register; thermal capacity to start
Start Data: Avg Start time, Avg Start Current, Measured Capacity to start, time since last start
RTD Data (Option): Temperature readings from up to 12 RTDs (6 stator RTDs)
Voltage Metering: V, KW, KVAR, PF, KWH, Demand |