Acceleration Adjustments
Ramp types Voltage ramp or current ramp Starting torque 0 - 100% of line voltage or 0 - 600% of FLA Ramp time 1 to 120 seconds Current limit 200 - 600% |
Retentive Thermal Memory
Remembers the thermal condition of the motor even in the event of a power brown-out or black-out. Extrapolates motor temperature using a real-time clock. |
Deceleration Adjustments
Begin decel level 0 - 100% of line voltage
Stop level 0 to 1% less than begin decel
Decel time 0 - 60 seconds
Operation during overload Ramp down or coast-to-stop
Jog Settings*
Jog at set current 100 - 500% of FLA
Jog at set voltage 0 - 100% of line voltage
Voltage jog max time 0 - 20 seconds |
Phase Current Imbalance/Loss Protection
Imbalance trip level 5 - 30% current between any two phases
Imbalance trip delay 0 - 20 seconds
Phase loss Trips on any phase current loss
Electronic Shear Pin Protection
Shear pin trip level 50 - 300% of motor FLA
Shear pin trip delay 0 - 20 seconds
|
Kick Start Settings
Kick start 0 - 100% of line voltage
Kick start time 0.1 - 2 seconds
Programmable Output Relays
Three (3) relays can be individually programmed for change of state indication for any one of 18 conditions.
Type / Rating FORM C (SPDT), rated 5 amps, 240VAC max (1200VA) |
Load Loss Trip Protection
Under current trip level 10 - 90% of motor FLA
Under current trip delay 0 - 20 seconds
Coast Down (Back Spin) Lockout Timer
Coast down time 0 - 60 minutes |
Start & Run Protection
Two programmable overload trip curves allow for the thermal capacity required to start the load while providing motor overload protection needed during the run time.
Start: Programmable for Class 5 - 30
Run: Programmable for Class 5 - 30, enabled when starter detects motor is "At-Speed"
Reset: Manual or automatic, selectable via programming
The XLD Series recognizes motor cool-down rates are a function of the run time and that sometimes a motor will cool faster if allowed to run.
Real-Time Thermal Modeling
Continuously calculates motor operating temperature even when your motor isn’t running. Knows when your motor is cool enough for a successful restart |
Starts-per-Hour Lockout Timer
Starts-per-hour 1 - 10 successful starts per hour
Time between starts 0 - 60 min. between start attempts
Phase Rotation Phase sequence insensitive
Shorted Load
During start, injects voltage for ? second and will trip if it sees a current surge
Short Circuit Trips in 12.5 ms at 10x unit current rating during run
Shorted SCR
Trips on a voltage drop of less than 1? V across any SCR pair
Shunt Trip
Relay trips on current flow while in the OFF mode (multiple shorted SCRs)
Over Temperature
Thermal sensors on heat sinks trip when temperature exceeds 185° F |