| Design |
| Type of Load |
3-phase AC induction motors |
| AC Supply Voltage (Motor Voltage) |
Direct: 200 - 600VAC, ± 10%, 50/60hz With 120V PTs: 690 - 15,000VAC |
| Current Range |
1 - 2000 Amps in 3 frame ratings |
| Sevice Factor |
Programmable from 1.00 to 1.30 for NEMA design motors |
| Current Measurement |
3 window CTs on units up to 75A, external CTs for higher ratings (meets NEC requirments for 3-leg protection) |
| Power Wiring |
Direct feed-through or external CT lead feed-through |
| LED Display and Keypad |
7-segment, 4-digit alpha-numeric display designed for use in high ambient light conditions. Full function, 4- quadrant navigation keys for easy access to status information and programmable functions |
| LED Status Lights |
10 LED indicators on the front panel for relay status |
| Control |
| Control Voltage |
Universal voltage supply, 85 - 265VAC or DC, 50/60Hz |
| Multi-function Digital Input |
One (1) dry contact input for Timer Start, Remote Start or Remote Trip |
| Fault Reset |
Manual reset via the keypad or cycle control power for remote reset |
| Programmable Output Contacts |
One (1) Form C (SPDT) 5A, 240VAC maximum One (1) Form A (SPST) 10A maximum, 1/2 HP @ 240VAC 29 programmable trip functions |
| Event Timer Control |
24 hr, 7 day, 7 event timer allows automatic start w/ batch run time control |
| Batch Run Timer Control |
Minimum run timer (resumes timing if stopped) or permissive run timer (only runs during set time). Time setting: 1 - 9999 minutes. |
| Protection |
| Overload Protection Method |
Real-time Motor Thermal Modeling uses current sensors and microprocessor to continuously calculate motor temperature |
| Retentive Thermal Memory |
Remembers the thermal condition of the motor even if control power is lost. Thermal register is adjusted for Off-time when power is restored. |
| Dual Overload Curve Settings |
Two separately programmable overload trip curves; one for starting and one for running. OL trip range: Class 5 - 30. |
| Learned Dynamic Reset |
Automatically adjusts other settings to compensate for programmed Service Factory. Adjustment Range: 1.0 - 1.15 SF. |
| Programmable Service Factor |
Automatically adjusts other settings to compensate for programmed Service Factory. Adjustment Range: 1.0 - 1.15 SF. |
| Current Imbalance Protection |
Monitors phase-to-phase current levels and trips if imbalance exceeds setting. Setting: Off or 5 - 30% of FLA with 1-20 second delay. |
| Phase Loss / Sequence Protection |
Trips if any phase < 20% FLA. Sequence selectable A-B-C, C-A-B or Off. |
| Current Trip |
Over Current |
| Under Current |
|
| Electronic shear-pin/shock relay. Off or 50-300% FLA, 1-20sec delay |
| Load-loss/loss of prime. Setting: Off or 10-90% FLA, 1-60sec delay |
|
| Over Voltage Trip (any phase) |
Setting: Off or 1-10% of set voltage with 1-20 second delay |
| Under Voltage Trip |
On Startup |
| At Full Speed |
|
| Setting: Off or 1 - 20% of set voltage with 1-120 second startup time |
| Setting: Off or 1 - 20% of set voltage with 1-20 second trip delay |
|
| Load Monitor |
Under or over kW trip or alarm. Setting: Off or 20 - 100% of motor kW with 1-20sec delay |
| Power Factor Monitor |
Leading or lagging PF, trip or alarm. Setting: Off or 0.1 - 1.0PF (lead or lag) with 1-20 second delay |
| Frequency Monitor |
Over or under programmed frequency. Setting: Off or 1-10Hz with 1-20sec delay |
| Equipment Ground Fault Protection |
Electronic residual current protection method, no additional CTs needed. Setting: Off or 5-90% of CT with 1-60sec delay |
| Short Circuit / Shorted Load |
Peak current quick trip (electronic fuse). Trip level: Off or 800-1400% FLA with 0.1 - 0.5sec delay |
| Restart Delay Timer |
Programmable delay of restart after a power failure. Setting: 0 - 999 sec. |
| Starts-per-Hour Lockout |
Program maximum starts-per-hour in adherence with motor design limitations. Setting: Off or 0 - 10 starts/Hr. |
| Minimum Time between Starts |
Used with or without starts-per-hour protection to prevent short cycling of motor. Setting: Off or 1 - 60 minutes between starts |
| Coast-Down Timer |
Back spin or anti-windmillling protection prevents restart after stop command has been given. Time setting: Off or 1 - 3600 seconds. |
| Metering |
| Amp Meter (each phase) |
Default is Phase A, scroll up or down for phases B, C and ground. 0 - 9999A (999A for ground),
± 2% accuracy |
| Volt Meter (each phase) |
0-600V, or 1-15kV, ± 2% accuracy. Displays total voltage imbalance as %. |
| Elapsed Time Meter |
Running time from at-speed detection. Resettable only with passwrd.
Range: 0 - 9,999,999.9 hours. |
| Run Cycle Counter |
Counts number of starts (at-speed) for maintenance, etc. Resettable only with password.
Range: 0 - 99,999,999 counts. |
| Power Metering |
kW, kWHr, kVA, kVAR, or MW, MWHr, MVA, MVAR.
0 - 9999 units, ± 2% accuracy |
| Power Factor Metering |
Leading (inductive) or lagging (capacitive), 0.1 - 1.0 PF |
| Display |
| Fault Display |
Fault code indicator plus 10 LEDs for phase and trip status. |
| Fault Event Recorder |
Records and displays previous three (3) fault trips (stored in non-volatile memory). Time and date
stamped. Cleared only with password. |
| Thermal Capacity |
Real-time display of motor's remaining thermal capacity after starting or running. Value shown as 0 - 100%
(counts upwards while cooling). |
| Remaining Time |
View values of lockout times such as time-between-starts or coast-down timer. View process timer or time clock values. |
| Environmental
Conditions & Approvals |
| Standard Packaging |
Protected Chassis (IP00) with DIN rail adaptor |
| Remote Display Mounting |
Built in operator interface can be remote mounted up to 10ft (3 meters) away. NEMA 4/12 mounting kit
optional. |
| Altitude |
Up to 10,000 feet (3000 meters) without derating |
| Ambient Temperature |
0° C to 50°C (32°F to 122°F), 0 to 95% relative humidity |
| Approvals |
UL, CUL, CE |
| |
|
| |
|