Power Components
6 SCRs in inverse parallel pairs for full phase angle
soft start control
1600V PIV rating on all units
RC snubber for dv/dt protection of each SCR pair |
Jog
Dry contact closure selects a non-ramping Jog
function at an adjustable torque |
Line Voltage Range
200 to 600 VAC, 3 phase +10% -15% on all units,
50/60Hz |
Kick Start
10 - 100% starting torque for 0.1 - 2 seconds |
Current Ratings
18 - 1250A depending on unit selection
Range of each unit is 50-100% of maximum |
Pump-Flex™ Deceleration Ramp
Fully adjustable to match field conditions:
Begin Decel setting, 0 - 100% of line voltage
Decel ramp time, 1 - 60 seconds
End Decel setting (Off ), 0 - 1% of Begin setting |
AC Supply Voltage
User supplied 120VAC +10% -15% tolerance, 60Hz
Optional 240VAC 50Hz control available |
Restart Delay Timer (Sequential Start Delay)
Programmable time delay 1 - 999 seconds after loss
of control power for staggered restarts |
Overload Capacity (% of motor FLA)
Standard Duty: 350% for 30 seconds, 1.0 SF
Heavy Duty: 500% for 30 seconds, 1.15 SF |
Time Clock Controller
24 hour/7 day time clock to provide automatic start
Up to 7 start events per day
Select operation from 1 through 7 days per week
Run time determined by process control timer |
Bypass Contactor
Standard on all units
Standard Duty: Shunt rated bypass
Heavy Duty (Across-the-Line) line start rated bypass |
Process Control Timer (choice of either)
Minimum Run (Batch) Timer
1- 999 minutes
Runs until time expires, resets only if expired
Resumes and finishes if stopped or power is lost
Permissive Run Timer
1- 999 minutes
Only allows operation during active run time |
Start/Stop Control Choices
2-wire Run-Stop using dry contacts
3-wire Start/Stop with built-in seal in contact
N.C. Interlock input (dry contact) for remote devices |
RS-485 Serial Communications
Up to 247 starters per link
Modbus RTU protocol built-in
Full programming over the serial link
Programmable remote starter control |
Ramp Control Choices (4 built-in)
Voltage Ramp
Voltage Ramp with Current Limit
CLT© Closed Loop Torque Ramp (Current Ramp)
Current Step (current limit only)
Ramp times adjustable 1 - 120 seconds
Current Limit adjustable 200 - 600% of FLA |
Operator Interface
Tactile feedback keypad
Easy to read LED display
Run and fault
status indicators |
Dual Ramps
Select via dry contact closure between any
combinations of the above |
Electronic Shear Pin Protection
Trip level: 100 - 300% of motor FLA with trip delay |
Start & Run Protection
Two programmable overload trip curves allow for the
thermal capacity required to start the load while providing
motor overload protection needed during the run time.
Start: Programmable for Class 5 - 30
Run: Programmable for Class 5 - 30, enabled when starter
detects motor is "At-Speed"
Reset: Manual or automatic, selectable via programming.
Remote reset available. |
Motor Duty Cycle Protection
Back-spin/coast-down, starts-per-hour or minimum
time between starts lockouts. Restart delay after a
power failure. |
Real-Time Thermal Modeling
Continuously calculates motor operating temperature even
when the motor is not running. |
Short Circuit
Trips at 10x unit current rating during run. Checks for
shorted load prior to each start. |
Retentive Thermal Memory
Remembers the thermal condition of the motor even in the
event of a power brown-out or black-out when power is
restored. Extrapolates motor temperature using a real-time
clock. |
Shorted SCR
Locks out on any single shorted SCR (defeatable) or
can provide shunt trip function if multiple SCRs short
or bypass contactor is welded closed. |
Dynamic Reset Capacity
Overload will not reset until thermal capacity in the motor is
sufficient for a successful restart. Starter learns and retains this
information from previous starts. |
Metering
Monitors phase current, ground current and motor
thermal capacity. |
Motor Temperature
PTC thermistor input can also be used for E-stop or external
overload relay. |
Phase Loss
Trips on phase current or voltage loss |
Equipment Ground Fault
Residual current method with adjustable trip delay. |
Phase Rotation
Phase rotation trip can be set to A-B-C, A-C-B or disabled. |
Phase Current Imbalance/Loss Protection
Trip level: 5 - 30% current imbalance between any two
phases with trip delay |
|